PCC  414 Emergency  Procedures 

  Constellation Place: PCC414. 700 Constellation Drive, Mississauga, ON 

CARRY OUT RESET OR SIGNAL SILENCE ONLY AS INSTRUCTED BY THE FIRE CAPT.

 

 

TO RESET THE FIRE PANEL CARRY OUT THE FOLLOWING:

 

  1. PUSH "SYSTEM RESET" BUTTON ON RIGHT HAND FIRE PANEL.

 

IF SYSTEM DOES NOT RESET:

 

  1. ATTEMPT A SECOND RESET.
  2. IF SECOND RESET DOESN'T WORK, ASK FIRE CAPT. FOR AUTHORIZATION TO SILENCE SIGNALS.
  3. SILENCE THE ALARM SIGNALS BY PRESSING THE "SIGNAL SILENCE" BUTTON.
  4. TURN BOTH ELEVATOR RECALL SWITCHES TO "OFF".
  5. TURN ELEVATOR PRESSSURE FAN SWITCH (UPPER LEFT PANEL) TO "OFF" (PULL OUT TO MOVE).
  6. CONDUCT FIRE WATCH IN AREA WHERE ALARM WILL NOT RESET.
  7. NOTIFY PROPERTY MGMT, GROUP 4 OF ALARM STATE AND FIRE WATCH.
  8. PREPARE INCIDENT REPORT.


IF A "SIGNAL SILENCE" IS CARRIED OUT THE FOLLOWING MUST BE DONE IF ANOTHER FIRE ALARM SOUNDS:


  1. TURN BOTH ELEVATOR RECALL SWITCHES TO "ON".
  2. TURN ELEVATOR PRESSSURE FAN SWITCH (UPPER LEFT PANEL) TO "ON" (PULL OUT TO MOVE).


ELEVATOR RESET PROCEDURES

 

1. NORMAL RECALL

A NORMAL RECALL IS WHEN THE ELEVATOR WAS RECALLED TO THE GROUND FLOOR. THE PROCEDURE FOR RESET IS:

 

  1. FIRE PANEL SWITCH TO "OFF"
  2. ELEVATOR PANEL SWITCH TO "OFF"
  3. FIRE PANEL SWITCH TO "AUTO"
  4. ELEVATOR PANEL SWITCH TO "AUTO"

 

2. ALTERNATE RECALL

AN ALTERNATE RECALL IS WHEN THE FIRE DETECTION WAS IN THE AREA IMMEDIATELY TO THE FRONT OF THE MAIN FLOOR ELEVATOR DOORS. THE ELEVATORS RECALL TO THE SECOND FLOOR. THE PROCEDURE FOR RESET IS: 

  1. FIRE PANEL SWITCH TO "ON"
  2. ELEVATOR PANEL SWITCH TO "ON"
  3. FIRE PANEL SWITCH TO "OFF"
  4. ELEVATOR PANEL SWITCH TO "OFF"
  5. FIRE PANEL SWITCH TO "AUTO"
  6. ELEVATOR PANEL SWITCH TO "AUTO"